CHECK OUT OUR PROMOTIONS HERE

 

UL Type MV-105 Ampacities – Copper Conductors – Rated 5 kV to 35 kV

UL Type MV-105 Ampacities – Copper Conductors – Rated 5 kV to 35 kV

UL Type MV-105 Ampacities – Copper Conductors – Rated 5 kV to 35 kV
Toggle Icon

Utility Aluminum Cables

Category Link Icon

Nada Filipovic

23 June 2025

2026-07-24

Conductor Size
(AWG or kcmil)
Ampacity
Direct Buried (Touching)
(A)

Direct Buried (Spaced 7.5 in)
(A)

In Conduit In Air (Touching)
(A)

In Cable Tray (Spaced One Cable Diameter)
5 kV to 15 kV
(A)

In Cable Tray (Spaced One Cable Diameter)
25 kV to 35 kV
(A)

2
205
225
165
215
---
1
230
260
190
250
250
1/0
260
295
215
290
290
2/0
295
335
255
335
330
3/0
340
380
290
385
380
4/0
385
435
330
445
445
250
410
475
365
495
490
350
505
575
440
610
605
500
605
700
535
765
755
750
740
865
655
990
970
1000
830
1005
755
1185
1160
Conductor Size
(AWG or kcmil)
Ampacity
Direct Buried (Touching)
(A)

Direct Buried (Spaced 7.5 in)
(A)

In Conduit In Air (Touching)
(A)

In Cable Tray (Spaced One Cable Diameter)
5 kV to 15 kV
(A)

In Cable Tray (Spaced One Cable Diameter)
25 kV to 35 kV
(A)

2023 NEC Article
Article 315.60(F)
Article 315.60(F)
Article 315.60(E)
Article 392.80(B)(2)(2)
Article 392.80(B)(2)(2)
2023 NEC Table
Table 315.60(C)(19) One Circuit
Table 315.60(C)(15) One Circuit
Table 315.60(C)(7)
Table 315.60(C)(3)
Table 315.60(C)(3)
Cable Configuration
2023 NEC Figure 315.60(D)(3), Detail 7
2023 NEC Figure 315.60(D)(3), Detail 9
Touching
Single Layer, Spaced One Cable Diameter
Single Layer, Spaced One Cable Diameter
Installation Conditions
Earth Ambient = 20 deg C (68 F)
Earth Thermal Resistivity = 0.90 deg C m / W
Depth of Burial = 36 in
Earth Ambient = 20 deg C (68 F)
Earth Thermal Resistivity = 0.90 deg C m / W
Depth of Burial = 36 in
Ambient Air = 40 deg C (104F)
Ambient Air = 40 deg C (104 F)
Ambient Air = 40 deg C (104 F)